ESTIMATION OF CORONA ELECTRICITY LOSSES IN 220–750 KV OVERHEAD LINES TAKING INTO ACCOUNT THE DESIGN PARAMETERS OF SUPPORTS
Article_2 PDF (Українська)

Keywords

climatic losses of electric energy
losses on the crown
overhead power lines
configuration of supports
lightning protection cable

How to Cite

Kuchanskyi, V., et al. “ESTIMATION OF CORONA ELECTRICITY LOSSES IN 220–750 KV OVERHEAD LINES TAKING INTO ACCOUNT THE DESIGN PARAMETERS OF SUPPORTS”. Proceedings of the Institute of Electrodynamics of the National Academy of Sciences of Ukraine, no. 72, Dec. 2025, p. 015, doi:10.15407/publishing2025.72.015.

Abstract

The article describes an improved mathematical model for estimating climatic losses of electric energy on the crown in overhead power lines. The model is supplemented by taking into account the equivalent height of the wire above the ground h according to the parameters given in the Rules for the «Arrangement of Electrical Installations (PUE)», as well as the possibility of calculating processes in three phases using the method of symmetrical components. The procedure for determining the initial electric field strength on the surface of wires for bad weather conditions is specified. The significant influence on the results of calculations of electrical energy losses on the crown of the supports and the presence of a lightning protection cable (GZT) is proven. The results obtained indicate the feasibility of taking into account the configuration of the supports and the presence of GZT when forming tabular values ​​of specific power losses and average annual specific losses on the crown given in regulatory documents, which will increase the accuracy of estimating climatic losses of electric energy. Ref. 20, tabl. 3, fig. 4.

https://doi.org/10.15407/publishing2025.72.015
Article_2 PDF (Українська)

References

1.IEC/TR 63097:2017 Smart grid standardization roadmap. 2017. 315 p.

2.Kuznetsov V.G., Tugay Y.I., Kuchanskyy V.V. Influence of corona discharge on the internal ovevoltages in highway electrical networks. Tekhnichna Elektrodynamika. 2017. No 6. Pp. 55–60. DOI: https://doi.org/10.15407/techned2017.06.055 URL: https://techned.org.ua/index.php/techned/article/view/753 (Accessed 13.11.2025). (Ukr)

3.Suleymanov V.N., Katsadze T.L. Electric networks and systems: Textbook. Kyiv: NTUU KPI, 2008. 504 p. (Rus)

4.Kuchanskyy V.V., Zaitsev I.O. Corona discharge power losses measurement systems in extra high voltage transmissions lines. IEEE 7th International Conference on Energy Smart Systems (ESS), 2020. Pp. 48–53. DOI: https://doi.org/10.1109/ESS50319.2020.9160088

5.Gai O.V., Kulyk B.I. High Voltage Engineering: Textbook. Kyiv: NUBIP Publishing House of Ukraine, 2021. 710 p. (Ukr)

6.Katsadze T.L. Fundamentals of mechanical calculations of overhead power transmission lines. Kyiv: Igor Sikorsky Kyiv Polytechnic Institute, Publishing House Polytechnics, 2019. 336 p. (Ukr)

7.RD 34.20.172-74 Guidelines for accounting for corona losses and corona interference in the selection of overhead power lines of alternating current 330-750 kV and direct current 800-1500 kV. (Rus)

8.Brzhezitsky V.O., Isakova A.V., Rudakov V.V. High voltage engineering and electrophysics. Kharkiv: NTU KhPI. Tornado, 2005. 930 p. (Ukr)

9.Shcherba A.A., Peretyatko Y.V. Theoretical Fundamentals of Electrical Engineering 1. Direct and alternating current electrical circuits. Four-pole. Kyiv: Igor Sikorsky Kyiv polytechnic institute, 2021. 116 p. (Ukr)

10.Blinov I.V, Zaitsev I.O., Kuchanskyy V.V. Problems, methods and means of monitoring power losses in overhead transmission lines. Systems, Decision and Control in Energy I. Studies in Systems, Decision and Control, V. Babak, V. Isaienko, A. Zaporozhets. Ed, Vol. 298, 2020. Springer, Cham. DOI: https://doi.org/10.1007/978-3-030-48583-2_8

11.Zaitsev I.O., Kuchanskyy V.V. Corona discharge problem in extra high voltage transmission line. Systems, Decision and Control in Energy II, Studies in Systems, Decision and Control, A. Zaporozhets, V. Artemchuk. Ed., 2021. Pp. 3–30. DOI: https://doi.org/10.1007/978-3-030-69189-9_1

12.Rules for the arrangement of electrical installations, approved by the order of the Ministry of Energy and Coal Industry of Ukraine dated 07/21/2017. No 476. URL: https://zakon.rada.gov.ua/rada/show/v0476732-17#Text (Accessed 13.11.2025) (Ukr)

13.SOU-N EE 40.1 – 37471933-82 Methodological recommendations for determining technological consumption of electric energy in transformers and power transmission lines. URL: https://zakon.rada.gov.ua/rada/show/v0399732-13#Text (Accessed 13.11.2025) (Ukr)

14.Kyryk V.V. Electrical systems and networks: textbook. Kyiv: KPI named after Igor Sikorsky, Polytechnic Publishing House, 2021. 324 p. (Ukr)

15.Szegeda M. S. Electric networks and systems: textbook. Lviv: Publishing House of the National University Lviv Polytechnic, 2007. 488 p. (Ukr)

16.Buslavets O.A., Koval Ya.M. Calculation of electric power losses due to corona in the networks of NEK Ukrenergo. Electric networks and systems. 2013. No 2. Pp. 56–68. (Rus)

17.Kuchanskyy V.V., Tugay Y.I., Tugay I.Y. Substantiation of the design of split-phase overhead inter-system power transmission lines. Visnyk Vinnytskoho politekhnichnoho instytutu, 2024. Vyp. 6. Pp. 27–33. DOI: https://doi.org/10.31649/1997-9266-2024-177-6-27-33 (Ukr)

18.Olubakinde E. Study of the influence of the split-phase capacitance on the power losses associated with corona discharge. Bulletin of the National Technical University KhPI. Series: Energy: reliability and energy efficiency, issue 1 (4), July 2022, Pp. 56–61. DOI: https://doi.org/10.20998/2224-0349.2022.01.08 (Ukr)

19.Katsadze T., Chyzhevsky V., Buslova N. Cherkashyna V. Determination of component losses of active power in long-distance ac power transmission. Tekhnichna electrodynamika. 2022. No 4. Pp. 54–58. DOI: https://doi.org/10.15407/techned2022.04.054 (Ukr)

20.Kuchansky V.V., Zaitsev E.O., Kovalenko O.M. Analysis of experimental estimates of power losses during coronation of airy intersystem power transmission lines, Visnyk VPI. 2024. Vol. 4. Pp. 22–29. DOI: https://doi.org/10.31649/1997-9266-2024-175-4-22-29 (Ukr)

Creative Commons License

This work is licensed under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License.

Copyright (c) 2025 В.В. Кучанський, О.В. Гай, В.М. Бодунов , А.О. Ворушило, Г.А. Гай

Downloads

Download data is not yet available.